CVE-2022-43110

Voltronic Power ViewPower through 1.04-21353 and PowerShield Netguard before 1.04-23292 allows a remote attacker to configure the system via an unspecified web interface. An unauthenticated remote attacker can make changes to the system including: changing the web interface admin password, view/change system configuration, enumerate connected UPS devices and shut down connected UPS devices. This extends to being able to configure operating system commands that should run if the system detects a connected UPS shutting down.

  • Published: Aug 22, 2025
  • Updated: Nov 16, 2025
  • CVE: CVE-2022-43110
  • Severity: Critical
  • Exploit:

CVSS v3:

  • Severity: Critical
  • Score: 9.8
  • AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H